the modbus address in the KDU1A_set_sequence function block is incorrect.
In the function block, edit the "currentsequence_address" value to 7371 (instead of 7373).
The comment is also incorrect, the modbus holding register for current sequence is 7372 base-1 which becomes 7371 base-0 (not 7374 and 7373).